Three-phase Balanced Supply
(Saturday, May 8, 2010)
Three-phase Balanced Supply
In the module, containing six lessons (12-17), the study of circuits, consisting of the linear elements - resistance, inductance and capacitance, fed from single-phase ac supply, has been presented. In this module, which may also be termed as an extension of the previous one, containing three lessons (18-20), the solution of currents in the balanced circuits, fed from three-phase ac supply, along with the measurement of power, will be described.
In this (first) lesson of this module, the generation of three-phase balanced voltages is taken up first. Then, the two types of connections (star and delta), normally used for the above supply, followed by line and phase quantities (voltages and currents) for the connections, in both supply and load sides (both being balanced), are described.
Keywords: Three-phase balanced voltage, star- and delta-connections, balanced load.
After going through this lesson, the students will be able to answer the following questions:
1. How to generate three-phase balanced voltages?
2. What are the two types of connections (star and delta) normally used for three-phase balanced supply?
3. What are meant by the terms - line and phase quantities (voltages and currents), for the two types of connections in both supply and load sides (both being balanced)?
Generation of Three-phase Balanced Voltages
In the first lesson (No. 12) of the previous module, the generation of single-phase voltage, using a multi-turn coil placed inside a magnet, was described. It may be noted that, the scheme shown was a schematic one, whereas in a machine, the windings are distributed in number of slots. Same would be the case with a normal three-phase generator. Three windings, with equal no. of turns in each one, are used, so as to obtain equal voltage in magnitude in all three phases. Also to obtain a balanced three-phase voltage, the windings are to be placed at an electrical angle of with each other, such that the voltages in each phase are also at an angle of with each other, which will be described in the next section. The schematic diagram with multi-turn coils, as was shown earlier in Fig. 12.1 for a single-phase one, placed at angle of with each other, in a 2-pole configuration, is shown in Fig. 18.1a. The waveforms in each of the three windings (R, Y & B), are also shown in Fig. 18.1b. The windings are in the stator, with the poles shown in the rotor, which is rotating at a synchronous speed of (r/min, or rpm), to obtain a frequency of °120°120°120sN()120/)(sNpf⋅= (Hz), pbeing no. of poles [2=p] (see lesson no. 12).
Version 2 EE IIT, Kharagpur
Fig. 18.1 (a) Schematic diagram of
Three-phase Voltages for Star Connection
The connection diagram of a star (Y)-connected three-phase system is shown in Fig. 18.2a, along with phasor representation of the voltages (Fig. 18.2b). These are in conti- nuation of the figures 18.1a-b. Three windings for three phases are R (+) & R'(−),Y (+) & Y'(−), and B (+) & Y'(−). Taking the winding of one phase, say phase R as an example, then R with sign (+) is taken as start, and R' with sign (−) is taken as finish. Same is the case with two other phases. For making star (Y)-connection, R', Y' & B' are connected together, and the point is taken as neutral, N. Three phase voltages are:
θsinmRNEe=; )120(sin°−=θmYNEe;
)120(sin)240(sin°+=°−=θθmmBNEEe
It may be noted that, if the voltage in phase R () is taken as reference as stated earlier, then the voltage in phase Y() lags by , and the voltage in phase B() lags by , or leads by . The phasors are given as: RNeYNeRNe°120BNeYNe°120RNe°120 RR' Y' B Y B' N S 120º 120º 120º
Version 2 EE IIT, Kharagpur
)0.00.1(0jEERN+=°∠: )866.05.0(120jEEYN−−=°−∠; )866.05.0(120jEEBN+−=°+∠.
The phase voltages are all equal in magnitude, but only differ in phase. This is also shown in Fig. 18.2b. The relationship between Eand ismE2/mEE=. The phase sequence is R-Y-B. It can be observed from Fig. 18.1b that the voltage in phase Y attains the maximum value, after from the time or angle, after the voltage in •+++--ERNBB′EBNEYNY-Y′(a) RNBYRR′-VYN 30°30°30°120°120°120°VBN-VRNVBRVYN-VBNVRNVRY(b) VYBFig. 18.2 (a) Three-phase balanced voltages, with the source star-connected (the phase sequence, R-Y-B) (b) Phasor diagram of the line and phase voltages
Version 2 EE IIT, Kharagpur
phase R attains the maximum value, and then the voltage in phase B attains the maximum value. The angle of lag or lead from the reference phase, R is stated earlier.
Reversal of phase sequence from R-Y-B to R-B-Y
If the phase sequence is reversed from R-Y-B to R-B-Y, the waveforms and the corresponding phasor diagram are shown in figures 18.3 (a-b) respectively. It can be observed from Fig. 18.3a that the voltage in phase B attains the maximum value, after 120θ= from the time (or angle), after the voltage in phase R attains the maximum value, and then the voltage in phase Y attains the maximum value. The angle of lag or lead from the reference phase, R is stated earlier. The same sequence is observed in the phasor diagram (Fig. 18.3b), when the phase sequence is reversed to R-B-Y.
Version 2 EE IIT, Kharagpur
Relation between the Phase and Line Voltages for Star Connection
Three line voltages (Fig. 18.4) are obtained by the following procedure. The line voltage, is RYE
)]866.05.0()01[(1200jjEEEEEEYNRNRY−−−+=°−∠−°∠=−=
°∠=+=303)866.05.1(EjE
The magnitude of the line voltage, is RYE3times the magnitude of the phase voltage , and leads by . Same is the case with other two line voltages as shown in brief (the steps can easily be derived by the procedure given earlier). RNERYERNE°30
°−∠=°+∠−°−∠=−=903120120EEEEEEBNYNYB
°+∠=°∠−°+∠=−=15030120EEEEEERNBNBR
So, the three line voltages are balanced, with their magnitudes being equal, and the phase angle being displaced from each other in sequence by . Also, the line voltage, say , °120RYEleads the corresponding phase voltage, by RNE°30 VYB VYN VBR VBN VRY VRN -VYN 120°120°30°30°30°(b) 60° Fig. 18.3 (a) Three-phase balanced voltage waveforms with the source star-connected (the phase sequence, R-B-Y) (b) Phasor diagram of the line and phase voltages
Version 2 EE IIT, Kharagpur
Relation between the Phase and Line Voltages for Delta Connection
The connection diagram of a delta (Δ)-connected three-phase system is shown in Fig. 18.4a, along with phasor representation of the voltages (Fig. 18.4b). For making delta (Δ)-connection, the start of one winding is connected to the finish of the next one in sequence, for instance, starting from phase R, R' is to connected to Y, and then Y' to B, and so on (Fig. 18.4a). The line and phase voltages are the same in this case, and are given as
°+∠=°−∠=°∠=120;120;0EEEEEEBRYBRY • ••••+-R Y B + +- -EYBB B R R'ERYB' EBR(a) Y 'Y EBRERYEYB120°120°120°(b) Fig. 18.4 (a) Three-phase balanced voltages, with the source delta-connected (the phase sequence, R-Y-B) (b) Phasor diagram of the line and phase voltages
Version 2 EE IIT, Kharagpur
If the phasor sum of the above three phase (or line) voltages are taken, the result is zero (0). The phase or line voltages form a balanced one, with their magnitudes being equal, and the phase being displaced from each other in sequence by°120.
Currents for Circuit with Balanced Load (Star-connected)
A three-phase star (Y)-connected balanced load (Fig. 18.5a) is fed from a balanced three-phase supply, which may be a three-wire one. A balanced load means that, the magnitude of the impedance per phase, is same, i.e.,NBNYNRpZZZZ′′′===, and their angle is also same, as NBNYNRp′′′===φφφφ. In other words, if the impedance per phase is given as,ppppXjRZ+=∠φ, then NBNYNRpRRRR′′′===, and also VRYR Y B R R R L L L IRNIYNIBNN'(a) IBN'VBN'VRN'IRN' YYN'IYN' ΦΦΦ(b) 120°120°120°Fig. 18.5 (a) Circuit diagram for a three-phase balanced star-connected load (b) Phasor diagram of the phase voltages, and the line & phase currents
Version 2 EE IIT, Kharagpur
NBNYNRpXXXX′′′===. The magnitude and phase angle of the impedance per phase are: 22pppXRZ+=, and ()pppRX/tan1−=φ. For balanced load, the magnitudes of the phase voltages,NBNYNRpVVVV′′′=== are same, as those of the source voltages per phaseBNYNRNVVV==, if it is connected in star, as given earlier. So, this means that, the point, star point on the load side is same as the star point, of the load side. The phase currents (Fig. 18.5b) are obtained as, N′N
pNRRNpNRRNpNRZVZVIφφφ−∠=∠°∠=−∠′′′0
)120(120)120(pNYYNpNYYNpNYZVZVIφφφ+°−∠=∠°−∠=+°−∠′′′
)120(120)120(pNBBNpNBBNpNBZVZVIφφφ−°∠=∠°+∠=−°∠′′′
In this case, the phase voltage, RNV is taken as reference. This shows that the phase currents are equal in magnitude, i.e., (NBNYNRpIIII′′′===), as the magnitudes of the voltage and load impedance, per phase, are same, with their phase angles displaced from each other in sequence by °120. The magnitude of the phase currents, is expressed as (pppZVI/=. These phase currents are also line currents (BYRLIIII===), in this case.
Total Power Consumed in the Circuit (Star-connected)
In the lesson No. 14 of the previous module, the power consumed in a circuit fed from a single-phase supply was presented. Using the same expression for the above star-connected balanced circuit, fed from three-phase supply (Fig. 18.4a-b), the power consumed per phase is given by
()ppppppppIVIVIVW,coscos⋅⋅=⋅⋅=φ
It has been shown earlier that the magnitude of the phase voltage is given by 3/LpVV= , where the magnitude of the line voltage is LV. The magnitudes of the phase and line current are same, i.e., LpII=. Substituting the two expressions, the total power consumed is obtained as
()pLLpLlIVIVWφφcos3cos3/3⋅⋅=⋅⋅⋅=
Please note that the phase angle, pφ is the angle between the phase voltage , and the phase current , . pVpI
Before taking up an example, the formulas for conversion from delta-connected circuit to its star equivalent and vice versa (conversion from star to delta connection) using impedances, and also ideal inductances/capacitances, are presented here, starting with circuits with resistances, as derived in lesson #6 on dc circuits.
Version 2 EE IIT, Kharagpur
Delta(Δ)-Star(Y) conversion and Star-Delta conversion
Before taking up the examples, the formula for Delta(Δ)-Star(Y) conversion and also Star-Delta conversion, using impedances as needed, instead of resistance as elements, which is given in lesson #6 in the module on DC circuit, are presented. The formulas for delta-star conversion, using resistances (Fig. 18.6), are,
32132RRRRRRa++= 32113RRRRRRb++= 32121RRRRRRc++=
The formulas for delta-star conversion, using resistance, are,
aaccbbaacbcbRRRRRRRRRRRRR++=++=1
baccbbabacacRRRRRRRRRRRRR++=++=2
caccbbacbabaRRRRRRRRRRRRR++=++=3
The derivation of these formulas is given in lesson #6. If three equal resistances () connected in delta, are converted into its equivalent star, the resistances obtained are equal, its value being RRRR===321RRRRRcba′====)3/(, which is derived using formulas given earlier. Similarly, if three equal resistances connected in star, are converted into its equivalent delta, the resultant resistances, using formulas, are equal (RRRRRR=⋅=′⋅===)3/(33321).
The formula for the above conversions using impedances, instead of resistances, are same, replacing resistances by impedances, as the formula for series and parallel combination using impedances, instead of resistances, remain same as shown in the previous module on ac single phase circuits.
Version 2 EE IIT, Kharagpur
The formulas for delta-star conversion, using impedances (Fig. 18.7), are,
32132ZZZZZZa++= 32113ZZZZZZb++= 32121ZZZZZZc++=
The formulas for delta-star conversion, using impedance, are,
aaccbbaacbcbZZZZZZZZZZZZZ++=++=1
baccbbabacacZZZZZZZZZZZZZ++=++=2
caccbbacbabaZZZZZZZZZZZZZ++=++=3
Please note that all the impedances used in the formula given here are complex quantities, like ,,,11aaZZφφ∠∠, having both magnitude and angle as given. The formulas can be derived by the same procedure as given in lesson #6.
An example is taken up, when three equal impedances connected in delta are to be converted into its equivalent star. The impedances are equal, both in magnitude and angle, such that ZZZZ===321, and φφφφ===321. The impedances connected in delta are of the form XjRZ±=∠φ. Using the formula given here, the impedances of the star equivalent are also equal, having the magnitude as
ZZZZZbba′====)3/( and angle as φφφφ===cba.
The angles of the equivalent impedance connected in star are equal to the angles of the impedances connected in delta. The impedances connected in delta are also equal, both in magnitude and angle, and are of the form )3/()3/()3/(XjRZZ±=∠=∠′φφ.
Similarly, if three equal impedances connected in star are converted into its equivalent delta, the magnitude and angle of the impedances using the formulas given here, are
ZZZZZ=′⋅===)3(321 and φφφφ===221 respectively. This shows that three impedances are equal, both in magnitude and angle, with its value being
XjRXjRZZ±=⋅±⋅=∠′⋅=∠)]3/(3[)]3/(3[)3(φφ
which can also be obtained simply from the result given earlier.
Version 2 EE IIT, Kharagpur
Now, let us use the above formula for the circuits (Fig. 18.8), using inductances only. The symbols used for the inductances are same (). The impedances of the inductances connected in delta, are computed as ,,,1aLL°∠=+=∠900.01111XLjZωφ, the angles in three cases are . The magnitudes of the impedances are proportional to the respective inductances as°90111LXZ∝=. Converting the combination into its equivalent star, the inductances using the formulas given here, are
32132LLLLLLa++= 32113LLLLLLb++= 32121LLLLLLc++=
These relations can also be derived. Further, these are of the same form, as has been earlier obtained for resistances. It may be observed here that the formulas for series and parallel combination using inductances, instead of resistances, remain same, as shown in the previous module on ac single phase circuits, and also can be derived from first principles, such as relationship of induced emf in terms of inductance, as compared with Ohm's law for resistance. The inductances are all ideal, i.e. lossless, having no resistive component. The formulas for star-delta conversion using inductances (conversion of star-connected inductances into its equivalent delta) are,
aaccbbaacbcbLLLLLLLLLLLLL++=++=1
baccbbabacacLLLLLLLLLLLLL++=++=2
caccbbacbabaLLLLLLLLLLLLL++=++=3
These are of the same form as derived for circuits with resistances.
If three equal inductances (LLLL===321) connected in delta, are converted into its equivalent star, the inductances obtained are equal, its value being
, which is derived using formulas given earlier. Similarly, if three equal inductances connected in star, are converted into its equivalent delta, the resultant inductances, using formulas, are equal (LLLLLcba′====)3/(LLLLLL=⋅=′⋅===)3/(33321).
Version 2 EE IIT, Kharagpur
The formulas for the circuits (Fig. 18.9) using capacitances are derived here. The symbols used for the capacitances are same (). The impedances of the inductances connected in delta, are computed as ,,,1aCC°−∠=−=∠900.0111XjXZCφ, the angles in three cases are (). The magnitudes of the impedances are inversely proportional to the respective capacitances as, °−90)/1()/1(111CCXXZC∝===ω. Converting the combination into its equivalent star, the resultant capacitances using the formulas given here, are
32132/1/1/1)/1()/1(/1CCCCCCa++=
or 132321133221CCCCCCCCCCCCCa++=++=
Similarly,
213322121313CCCCCCCCCCCCCb++=++=
313322132121CCCCCCCCCCCCCc++=++=
The capacitances in this case are all ideal, without any loss, specially at power frequency, which is true in nearly all cases, except otherwise stated. The formulas for star-delta conversion using capacitances (conversion of star-connected capacitances into its equivalent delta) are,
aaccbbaCCCCCCCC/1)/1()/1()/1()/1()/1()/1(/11++=
or cbacbCCCCCC++=1
Similarly,
cbaacCCCCCC++=2 cbabaCCCCCC++=3
If three equal capacitances (CCCC===321) connected in delta, are converted into its equivalent star, the capacitances obtained are equal, its value being
Version 2 EE IIT, Kharagpur
, which is derived using formulas given earlier. Similarly, if three equal capacitances connected in star, are converted into its equivalent delta, the resultant capacitances, using formulas, are equal (CCCCCcba′=⋅===)3(CCCCCC=⋅=′===3/)3(3/321).
The formulas for conversion of three equal inductances/capacitances connected in delta into its equivalent star and vice versa (star-delta conversion) can also be obtained from the formulas using impedances as shown earlier, only by replacing inductance with impedance, and for capacitance by replacing it reciprocal of impedance (in both cases using magnitude of impedance only, as the angles are equal ( for inductance and for capacitance). Another point to note is left for observation by the reader. Please have a close look at the formulas needed for delta-star conversion and vice versa (star-delta conversion) for capacitances, including those with equal values of capacitances, and then compare them with the formulas needed for such conversion using resistances/inductances (may be impedances also). The rules for conversion of capacitances in series/parallel into its equivalent one can be compared to the rules for conversion of resistances/inductances in series/parallel into its equivalent one. °90°−90
The reader is referred to the comments given after the example 18.1.
Example 18.1
The star-connected load consists of a resistance of 15 Ώ, in series with a coil having resistance of 5 Ώ, and inductance of 0.2 H, per phase. It is connected in parallel with the delta-connected load having capacitance of 90 Fμ per phase (Fig. 18.10a). Both the loads being balanced, and fed from a three-phase, 400 V, 50 Hz, balanced supply, with the phase sequence as R-Y-B. Find the line current, power factor, total power & reactive VA, and also total volt-amperes (VA). R Y B IRIYZ2
Version 2 EE IIT, Kharagpur
Solution
Hzf50=sradf/16.3145022=××==ππω
For the balanced star-connected load, Ω=15R
For the inductance coil, Ω=5r Ω=×==83.622.016.314LXLω
with the above values taken per phase.
The impedance per phase is,
Ω°∠=+=++=++=34.7294.65)83.6220()83.625(15)(1jjXjrRZL
For the balanced delta-connected load, FCμ90=
Converting the above load into its equivalent star, FCCμ303/903/1===
Ω=××==−1.106)103016.314/(1/1611CXCω
The impedance per phase is °−∠=−=′901.1061.1062jZ
In the equivalent circuit for the load (Fig. 18.10b), the two impedances, & 1Z2Z′ are in parallel. So, the total admittance per phase is,
°−∠+°+∠=′+=′+=901.106134.7294.651112121ZZYYYp310]425.9)46.146.4[(90009425.034.7201517.0−×+−=°+∠+°−∠=jj
1356.47006816.010)03.56.4(−−Ω°−∠=×−=j
The total impedance per phase is,
Ω+=°+∠=°−∠==)27.1080.99(56.4771.146)56.47006816.0/(1/1jYZpp
The phasor diagram is shown in Fig. 18.10c.
Taking the phase voltage, as reference, RNV
VVVVLpRN0.2313/4003/==== R Y B IRIYZ2Z1Z2Z2 = Z2 /3 Z1Z1IB(b) N Fig. 18.10 (a) Circuit diagram (Example 18.1) (b) Equivalent balanced star-connected circuit
Version 2 EE IIT, Kharagpur
The phase voltages are,
°+∠=°−∠=°∠=1200.231;1200.231;00.231BNYNRNVVV
So, the phase current, is, RNI
AjZVIpRNRN)162.10625.1(56.47575.156.4771.14600.231−=°−∠=°+∠°∠==
The two other phase currents are,
°+∠=°−∠=44.72575.1;56.167575.1BNYNII
As the total circuit (Fig. 18.5b) is taken as star-connected, the line and phase currents are same, i.e., AIIpL575.1==
Also, the phase angle of the total impedance is positive.
So, the power factor is lagp675.056.47coscos=°=φ
The total volt-amperes is kVAIVSpp0915.1575.123133=××=⋅⋅=
The total VA is also obtained as kVAIVSLL0915.1575.140033=××=⋅⋅=
The total power is WIVPppp737675.0575.12313cos3=×××=⋅⋅⋅=φ
The total reactive volt-amperes is,
VARIVQppp80556.47sin575.12313sin3=°×××=⋅⋅⋅=φ
This example can be solved by converting the star-connected part into its equivalent delta, as shown in Example 19.1 (next lesson). A simple example (20.1) of a balanced star-connected load is also given in the last lesson (#20) of this module.
After starting with the generation of three-phase balanced voltage system, the phase and line voltages, both being balanced, first for star-connection, and then for delta-connection (both on source side), are discussed. The currents (both phase and line) for VRNIBNVBNIYNVYNIRNΦ Φ Φ Fig. 18.10 (c) Phasor diagram VRY
Version 2 EE IIT, Kharagpur
balanced star-connected load, along with total power consumed, are also described in this lesson. An example is given in detail. In the next lesson, the currents (both phase and line) for balanced delta-connected load will be presented.
Version 2 EE IIT, Kharagpur
Problems
18.1 A balance load of (16+j12)Ω per phase, connected in star, is fed from a three-phase, 230V supply. Find the line current, power factor, total power, reactive VA and total VA.
18.2 Find the three voltages Van, Vbn, & Vcn, in the circuit shown in Fig. 18.11. The circuit components are: R = 10 Ω, jXL = j17.3 Ω.
Version 2 EE IIT, Kharagpur
List of Figures
Fig. 18.1 (a) Schematic diagram of three windings of stator for the generation of three phased balanced voltages (2-pole rotor).
(b) Three-phase balanced voltage waveforms with the source star-connected (the phase sequence, R-Y-B)
Fig. 18.2 (a) Three-phase balanced voltages, with the source star-connected (the phase sequence, R-Y-B)
(b) Phasor diagram of the line and phase voltages
Fig. 18.3 (a) Three-phase balanced voltage waveforms for the phase sequence, R-B-Y
(b) Phasor diagram of the line and phase voltages
Fig. 18.4 (a) Three-phase balanced voltages, with the source delta-connected (the phase sequence, R-Y-B)
(b) Phasor diagram of the line and phase voltages
Fig. 18.5 (a) Circuit diagram for a three-phase balanced star-connected load
(b) Phasor diagram of the phase voltages, and the line & phase currents
Fig. 18.6 Resistances connected in (a) Delta and (b) Star configurations
Fig. 18.7 Impedances connected in (a) Delta and (b) Star configurations
Fig. 18.8 Inductances connected in (a) Delta and (b) Star configurations
Fig. 18.9 Capacitances connected in (a) Delta and (b) Star configurations
Fig. 18.10 (a) Circuit diagram (Example 18.1)
(b) Equivalent balanced star-connected circuit
(c) Phasor diagram
Version 2 EE IIT, Kharagpur